Home / Tools / Condenser Sizing

Air-Cooled Condenser Designer

Tool · 05 of 06 · ASHRAE Ch. 35 THR factor
Step 1

Evaporator load

kW
From the Heat Load Calculator (Tool 1) — or your own number.
Step 2

System operating regime

Application
Step 3

Site ambient

°F
ASHRAE 0.4% design dry-bulb for your site.
°F
Air-on to refrigerant condensing ΔT. 22°F standard, 18°F premium quiet, 25°F compact.
Step 1 · Known Model

Pick your condensing unit

Selected condensing unit
No unit selected — click below.
Step 2

Site conditions

Application
°F
Manufacturers rate units at 95°F ambient — hot-climate derates apply.
kW
Compares unit's derated capacity vs your real load.

How this calculator works

The air-cooled condenser designer calculates required condenser capacity and recommends a class-typical unit using the Total Heat of Rejection (THR) method from ASHRAE Refrigeration Handbook 2022, Chapter 35. THR = refrigerating capacity × (1 + 1/COP), adjusted for compressor heat of compression at the specified saturated discharge temperature (SDT). Hot-climate ambient derate is applied: medium-temperature systems lose roughly 2.0%/°C above the ASHRAE reference ambient of 95°F (35°C); low-temperature systems lose roughly 2.7%/°C. A hard floor of 60% rated capacity is applied regardless of ambient. The tool warns when saturated condensing temperature (SCT) reaches 131°F (55°C) — above this threshold compressor warranty may be voided and oil carryover risk increases. Validated against Bitzer Software and Heatcraft NROES unit selection for hot U.S. summer design conditions (Phoenix, Las Vegas, Gulf Coast).

References: ASHRAE Refrigeration Handbook 2022 Ch. 35; Bitzer Refrigerants Report 25 (2022); Heatcraft Refrigeration Product Selection Guide.